CHECKLIST Verify Charge Controller - Renogy Wanderer 30 left in place, set to GEL setting verify internal battery - 3.61v verify program interval - 60 minutes Verify SDI sensor address and connectivity - SDI0 Soilvue SN 4048 verify Carrier Wave - Carrier Detected verify PAKBUS - 181 Verify Radio Control system - control system verified, code block at beginning of loop Verify Radio Control Interval - radio on at noon daily, off at 1 daily VERIFY PROGRAM RUN< ADJUST CLOCK - program run veified Verify Clock Settings - logger clock set to local time Verfiy table fill time - 41218 days to fill --Wiring Guide-- sw12_1 - soilvue power G - Ground C1 - SDI12 sw12_2 - Radio Power